1 PCS used YAMATAKE AUD300C1000 Flame Detector #LYQ007
1 PCS used YAMATAKE AUD300C1000 Flame Detector #LYQ007
|
Item
|
Specification
|
|
Model Number
|
AUD300C1000
|
|
Product Name
|
YAMATAKE AUD300C1000 Flame Detector, Industrial Precision Infrared Flame Detection Instrument
|
|
Brand & Manufacturer
|
YAMATAKE (AZBIL Corporation), 1-1 Marunouchi 2-chome, Chiyoda-ku, Tokyo 100-8310, Japan
|
|
Product Series
|
YAMATAKE AUD300 Series, Infrared (IR) Flame Detectors, Designed for Industrial Fire Early Warning & Protection Applications
|
|
Parameter
|
Minimum
|
Typical
|
Maximum
|
Unit
|
Notes
|
|
Detection Range (Hydrocarbon Flame)
|
0.5
|
15
|
30
|
m
|
Reference to n-heptane flame (1m×1m); Detection distance varies with flame size and environment; Reduced by 30-50% for alcohol/hydrogen flame with weak infrared radiation
|
|
Detection Angle
|
-
|
90
|
-
|
°
|
Horizontal detection angle; Vertical detection angle ±45°; Optimal installation with unobstructed view of protected area
|
|
Response Time
|
50
|
150
|
300
|
ms
|
From flame appearance to alarm output; Fast response for early fire warning; Configurable response time (0.1-1s) via controller
|
|
Wavelength Range
|
4.3
|
4.4
|
4.5
|
μm
|
Main detection wavelength (hydrocarbon flame characteristic peak); Reference wavelength 3.9μm; Narrow-band filter to eliminate interference[3]
|
|
False Alarm Rate
|
-
|
≤1
|
-
|
Time/Year
|
Under normal industrial environment; Anti-interference against sunlight, incandescent lamp, fluorescent lamp, high-temperature equipment (≤500℃)
|
|
Alarm Threshold
|
Low
|
Medium
|
High
|
-
|
3-level configurable via YAMATAKE HMI or controller; Adapt to different fire risk levels
|
|
Self-Diagnosis Function
|
-
|
-
|
-
|
-
|
Automatic detection of sensor failure, power supply abnormality, optical path blockage; Fault signal output (NO/NC configurable); Fault indication via LED
|
|
Parameter
|
Specification
|
|
Supply Voltage
|
DC 12~24V ±10%; AC 110~240V ±10% (Optional); Reverse Polarity Protection, Overvoltage Protection (≤36V DC)
|
|
Power Consumption
|
Typical 3W, Maximum 5W (Without Load, Ta=25℃); Low power consumption for continuous 24/7 operation
|
|
Alarm Output Channels
|
2 Channels, Relay Output (NO/NC Configurable); Contact Rating: 2A/250V AC, 3A/30V DC; Short-Circuit Protection
|
|
Signal Output
|
4~20mA DC Analog Output (Flame Intensity Signal); RS485 Digital Output (Modbus RTU Protocol); Compatible with YAMATAKE DCS/PLC Systems
|
|
Input Impedance
|
10kΩ (Signal Input), 100kΩ (Power Input); Optically isolated input/output to avoid interference
|
|
Isolation Voltage
|
2500Vrms (Input to Output, Power to Signal), 1 Minute Duration per IEC 61131-2 Standard
|
|
Indicator Lights
|
3 LED Indicators: Power (Green, Steady), Normal Operation (Green, Blinking), Alarm (Red, Steady), Fault (Yellow, Blinking); Visible from 5m distance
|
|
Remote Test Function
|
Support remote test via 4~20mA signal or RS485; Local test button (hidden) for on-site verification; Test duration 10~60s configurable
|
1 .Our company specializes in automation industrial control accessories. We have more than 100,000 products.
Including : frequency converter, servo driver, servo motor, data acquisition card, industrial camera, touch screen, circuit board, DCS module, soft starter, industrial computer,encoder... etc
2,We accept PayPal transaction. All products provided 60 days warranty. We can send the goods by fast express to all over world.
3. We can supply the product in brand new or used condition to meet your requirement.The picture and price show on our store is not real, before purchasing, please contact us to provide you with accurate quotation and real pictures.
4. If you can not find the product you need in our store, please contact us .we will check it for you.