Part Number: MX100-E-1D; Product Name: Yokogawa Industrial I/O Module
Brand: Yokogawa; Product Series: MX100 Series, designed for Yokogawa distributed control systems (DCS) and process automation platforms, responsible for analog signal acquisition and conversion.
Product Status: Original New Unit (In Stock); Product Category: Industrial Automation Analog Input Module, specialized in high-precision signal detection and stable data transmission for industrial process control.
Core Applications: Yokogawa CENTUM VP DCS, chemical process control, petroleum refining equipment, power plant monitoring systems, water treatment facilities and other scenarios requiring accurate analog signal measurement.
Core Features: High-precision analog signal conversion; Wide compatibility with Yokogawa DCS platforms; Industrial-grade anti-interference design; Hot-swappable support (optional); Real-time self-diagnosis function; LED status indication.
2. Electrical Specifications
2.1 Input Parameters
Input Type: Analog Input (Voltage/Current Selectable); Input Range: 4~20mA DC (Current), 0~10V DC (Voltage); Accuracy: ±0.1% FS (Full Scale) at 25℃.
Power Supply: DC 24V ±10% (Industrial Standard); Rated Power Consumption: ≤5W (Typical Operation); Rated Input Current: 0.2A (Typical), 0.5A (Peak).
2.2 Signal & Communication Parameters
Communication Interface: Yokogawa Proprietary Bus (Compatible with MX100 Series Backplane); Data Update Rate: 100ms (Adjustable); Signal Isolation: Galvanic Isolation (2.5kV AC, 1 Minute) Between Input and Backplane.
Input Impedance: ≥1MΩ (Voltage Input), ≤100Ω (Current Input); Signal Filtering: Low-Pass Filter (Cutoff Frequency Adjustable 1~100Hz); Resolution: 16 Bits.
2.3 Protection Functions
Over-Voltage Protection (OVP): ±30V DC (Input Terminal, Auto-Recovery); Over-Current Protection (OCP): 30mA DC (Input Loop, Latch Mode).
ESD Protection: ±8kV (Contact), ±15kV (Air, Per IEC 61000-4-2); Surge Protection: ±2kV (Line to Ground, Per IEC 61000-4-5); Reverse Polarity Protection: Supported (Built-in Diode for Power Supply).
3. Environmental Specifications
3.1 Operating Environment
Operating Temperature: 0℃~55℃ (No Derating); Storage Temperature: -40℃~85℃ (No Condensation).
Relative Humidity: 5%~95% RH (Non-Condensing, 0℃~55℃); Altitude: ≤2000m (Above Sea Level, Normal Operation).
Vibration Resistance: 10Hz~500Hz, 0.3G (X/Y/Z Directions, Continuous Operation, Per IEC 60068-2-6); Shock Resistance: 15G (11ms Duration, Half-Sine Wave, Per IEC 60068-2-27).
3.2 EMC Standards
Emission Standards: EN 55022 Class A, FCC Part 15 Class A; Immunity Standards: EN 61000-4-3 (Radiated Immunity 3V/m), EN 61000-4-4 (EFT ±1kV Power Line).
Protection Degree: IP20 (Module-Level); Pollution Degree: 2; Over-Voltage Category: Ⅱ (Industrial Environment).